F200K

  • Compact case with integrated flame sensor and switching amplifier
  • Intensity adjust in multiple steps
  • Digital circuit design for flame evaluation
  • Status indication by LEDs 24 VDC operating voltage
  • Two electronic channel system for fail safe operation and supervision
  • LED bar flame intensity indication and 4 (0) … 20 mA analog output
  • LED bar trend indication selectable for an optimum adjustment to the flame direction

Compact Flame Scanner F200K.

Power supply:

24 VDC ± 20 %, ≤ 4,0 W

Output contact:

≤ 42 VDC, ≥ 6 VAC/DC
≤ 0,5 A, ≥ 1,0 mA floating

Frequency range:

10 … 190 Hz (F200K1 …)
10/20/30 … 190 Hz (F200K2 …)

Safety time ‘operation’:

t ≤ 1 s (standard)
t ≤ 3 s (on request, at the factory)

Mode of operation:

Continuous operation

Protection class:

IP67
NEMA 4X

Operating temperature:

-40 °C … +75 °C  (IR-1 only up to +60 °C)

Dimension:

Total length: 180 mm
Diameter: 40/80 mm

Weight:

0,6 kg

Material:

Corrosion-resistant aluminium EN AW 6082 (seawater 2*; atmospheric condition 1*), nickel plated, varnished

* Comparative evaluation from 1 (very good) to 6 (unsuitable)

Approvals:

    

EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298:2012-11

CE Declaration of Conformity

  • 2009/142/EC (Gas Appliance Directive)
  • 2014/68/EU (Pressure Equipment Directive)