F300K

  • 3 operating modes, can be externally preselected, switchable during operation
  • 14 graduated frequency ranges
  • available as single or double sensor (IR/UV)
  • can be completely operated without opening the device (degree of protection IP67 is retained, even during commissioning)
  • Menu-guided configuration and commissioning
    with Flame ON/OFF self-learning function
  • Alignment assistance by means of a logical graphical display of flame data
  • Operation via graphic User Interface with status display (optional)
  • SIL 3 according to DIN EN 61508 part 1-7

Compact Flame Scanner F300K.

Supply voltage:

24 VDC ± 20 % ≤ 3,5 W

Flame and fault contact:

≤ 50 VDC, ≥ 6 VDC
≤ 0,5 A, ≥ 1,0 mA floating

Frequency range:

10 / … / 110 … 210 Hz
7 levels in the standard version

Safety time “Operation”:

t ≤ 1 sec. (standard)
t ≤ 1, 2, 3, 4, 5 sec. (selectable via password)

Operating mode:

Continuous operation

Degree of protection:

IP67
NEMA 4X

Operation temperature:

-40 °C … + 85 °C

Dimensions (HxT):

99×195,5 mm

Weight:

1,05 kg (aluminium)
3,6 kg (stainless steel)

Material:

Corrosion-resistant aluminium EN AW 6082 (seawater 2*; atmospheric condition 1*), anodised
or stainless steel

* Comparative evaluation from 1 (very good) to 6 (unsuitable)

Approvals:

EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298:2012-11

SIL 3 Confirmation

  • DIN EN 61508 part 1-7

CE Declaration of Conformity

  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • 2014/68/EU (Pressure Equipment Directive Cat. 4 module B+D)
  • 2009/142/EC (Gas Appliance Directive)