FMS
- Burner control
- Electronical compound, up to 5 channels
- Universal field bus to interface process control
- PC/Modeminterface
- Integrated load controller
- Integrated leakage test
- Integrated CO/O2 controller
- Sliding controlled fuel changed
- Simultaneous combustion of 2 fuels with variable mixture ratio
- Blow out of the burner lance
FMS.
Voltage supply: |
230 VAC +10 % -15 % 50/60 Hz |
Ambient temperature |
+0 °C … +60 °C |
Ambient temperature |
-25 °C … +60 °C |
Resolution per analogue input: |
999 digit, 10 bit |
Three-point-step: |
via external relay modules |
Recommended run time of the servomotor: |
30 s … 60 s |
Constant outputs |
0 … 10 V > 5 kΩ |
Load: |
0/4 … 20 mA < 600 Ω |
Digital signal inputs: |
16 via floating contact |
Number of curve-sets: |
2 per channel (e.g. for oil/gas dual-fuel burner) optional 4 or 8 |
BUS connection: |
Via 25-pole sub-D socket, communication processor optional for the systems:
|
Approvals: |
EC Type Examination Certificate (Module B) according to Directive 2014/68/EU
SIL 3 Confirmation
CE Declaration of Confomity
Marine Type Approval Certificate GL and LR |