Ignition Systems GFI

Sistemas de encendido GFI

Categoría:

Ignition Systems GFI.

Resume:

  • Low loss of pressure through optimisation
  • Immediate, repeatable ignition in every firing rate
  • Highest flame stability
  • Safe flame monitoring
  • Modular design
  • Available in SIL 2 or SIL 3
  • Intermittent or continuous operation
  • Maritime climate resistant aluminium housing or stainless steel type
  • Protection class up to IP 67
  • Thermal power up to 3,000 kW
  • Flame length up to 2,500 mm
  • Pilot burner length up to 15,000 mm
  • Fuel: natural gas, LPG (liquid propane gas), coke gas, refinery gas
  • Individually customised solutions

Supply voltage:

220 – 230 VAC (-15/+10 %). 50/60 Hz
120 – 127 VAC (-15/+10 %). 50/60 Hz

Ignition voltage:

5 kV/10 kV

Power consumption:

100 VA ignition transformer
≤5 KV flame scanner

Electrical connection:

Cable, prewired (standard), plug and socket connector with pre-assembled cabl

Cable length:

2 m – 100 m, Standard = 5 m

IP protection:

IP 65/IP 67

Housing:

Sea water resistant aluminium (standard) stainless steel (1.4301/1.4404)

Coating:

non (standard)
C2/C4 painting (option)

Tube length:

240 – 15.000 mm
standard = 1.200 mm

Tube:

Stainless steel 1.4301, heat resistant end tube14.841 (standard) Stainless steel 1.4571 heat resistant end tube 14.841 (option)

Fuel gas:

Natural gas, propane/butane (standard) coke oven gas, refinery gas (option)

Fuel gas supply pressure:

50 – 200 mbar above combustion pressure (standard) Orifice for higher pressure (option)

Air suppl pressurer:

Depending on the size

Cooling air flow:

Depending on the size, at least 50 % of combustion air flow

Approvals:

For SIL 2 ionisation flame monitoring device:

kiwa 2009/142/EG
kiwa Sil 2
CE0063CR1400

UL
IEC/IECEx, ATEX

For SIL 3 flame monitoring device F130I:

2009/142/EC
2014/68/EU
SIL 3