The grids are made by specifications of the customers. Therefore the technical data can be indicated only generally. In the case of concrete offers, and/or supplies a data sheet made particularly for the appropriate grid is provided.
Resume:
|
- Volume measurement of gaseous media in ducts, especially for comdustion air for firing applications
- With a minimum of differential pressure loss, compared to the conventional technology
- Short length of inlet- and outlet-stretch for laminar flow. Long air-ducts are not required anymore
- Stainless steel material
- Basic temperature range up to 400 °C
- Free of maintenance for use in clean air application
- Rectangular and circular grid versions are available
- With increased dust particles loading, flushing back can be done (option)
- Connection to the Differential Pressure Transmitter by impulse piping or on customer‘s request
|
Material
|
Stainless steel 1.4404
(other materials on request)
|
Pneumatic connection
|
Cutting ring connection SV12
(other types of connection on request)
|
Installation types
|
- Flange connection
- Welding execution
- Clamping connection for „Jacobrohr“
|
Applicable temperature range
|
+5°C…+400°C
(other temperature ranges on request)
|
Measuring media
|
All not aggressive, not explosive, gaseous media with well-known density
|
System pressure
|
-0,5…+0,5 bar (negative/positive pressure)
|
Repetition accuracy
|
Generally repetition accuracy ≤ +/- 1% from measured value
|
Measuring accuracy
|
- Calibrated grids on the test assembly ≤ +/- 1% from measured value
- Calculated grids +/- 5% from measured value
- Calibrated grids local ≤ +/- 2% from measured value
|